[shiftnav_toggle target="shiftnav-main" class="shiftnav-toggle-button" icon="bars"][/shiftnav_toggle]

Hoeford, Fareham

Overview

Client: Undisclosed
Location: Hoeford, Fareham
Objective: Installation & commissioning of 1 x 12/24MVA, 33/11.5kV transformer.

Scope of Work

  • Design, manufacture and testing of 1 x 12/24MVA, 33/11.5kV,  power transformer.
  • Full in-house routine, & partial discharge testing.
  • Delivery using a short file steerable trailer for site access then off-loading via hydraulic jacking and skating with a multi-directional skid.
  • Full commissioning works as per the customers specification which includes; insulation resistance of each winding, core & secondary circuits, transformer ratio check, vector group check by 3 phase low voltage energization of transformer, checks on all CTs & VTs for insulation resistance, ratio & magnetization curves, operation of tapchanger through range & operation of limit switches, operation of protection equipment, oil sampling for routine, water & dissolve gas analysis.

Description